B–63980EN/01
4. DESCRIPTION OF PARAMETERS
93
G23 When the power is turned on
0 : G22 mode (stored stroke check on)
1 : G23 mode (stored stroke check off)
#7
3403
#6
AD2
#5
CIR
#4 #3 #2 #1 #0
[Data type] Bit
CIR When neither the distance (I, J, K) from a start point to the center nor an arc
radius (R) is specified in circular interpolation (G02, G03):
0 : The tool moves to an end point by linear interpolation.
1 : P/S alarm No.022 is issued.
AD2 Specification of the same address two or more times in a block is:
0 : Enabled (Next specification is enabled.)
1 : Disabled (P/S alarm No.5074)
NOTE
1 When 1 is set, specifying two or more G codes of the same
group in a block will also result in an alarm being issued.
2 Up to three M codes can be specified in a single block, when
bit 7 (M3B) of parameter No.3404 is set to 1.
#7
3404
#6
EOR
#5
M02
#4
M30
#3 #2
SBP
#1
POL
#0
NOPM3B
[Data type] Bit
NOP When a program is executed, a block consisting of an O number, EOB, or
N number is:
0 : Not ignored, but regarded as being one block.
1 : Ignored.
POL For a command address allowing a decimal point, omission of the decimal
point is:
0 : Enabled
1 : Disabled (P/S alarm No.5073)
SBP Address P of the block including M198 in the subprogram call function
0 : Indicating a file number
1 : Indicating a program number
M30 When M30 is specified in a memory operation:
0 : M30 is sent to the machine, and the head of the program is
automatically searched for. So, when the ready signal FIN is returned
and a reset or reset and rewind operation is not performed, the
program is executed, starting from the beginning.
1 : M30 is sent to the machine, but the head of the program is not searched
for. (The head of the program is searched for by the reset and rewind
signal.)