B-63950EN/02 4.DESCRIPTION OF PARAMETERS
- 483 -
13220 Number of valid tools in tool management data
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Word
[Valid data range] 0 to 64 (Extended to 240 or 1000 by the addition of an option)
This parameter sets the number of valid tools in tool management
data.
13221 M code for tool life count restart
[Input type] Parameter input
[Data type] Word path
[Valid data range] 0 to 65535
When 0 is set in this parameter, this parameter is ignored.
When an M code for tool life count restart is specified, the counting of
the life of the tool attached at the spindle position is started. When
the type for counting the number of use times is selected, the target of
life counting is switched to the tool attached at the spindle position,
and the life count is incremented by 1.
When the type for counting time is selected, the target of life counting
is switched to the tool attached at the spindle position but no other
operations are performed. If the tool attached at the spindle position is
not a tool under tool life management, no operation is performed.
The M code set in parameter No. 6811 waits for FIN. However, the M
code set in this parameter does not wait for FIN.
The M code set in parameter No. 13221 must not be specified in a
block where another auxiliary function is specified.
The M code set in parameter No. 13221 does not wait for FIN. So, do
not use the M code for other purposes.
13222 Number of data items in the first cartridge
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Word
[Valid data range] 1 to 64 (Extended to 240 or 1000 by the addition of an option)
This parameter sets the number of data items used with the first
cartridge.