FANUC PMC-MODEL SD7
Programming Manual
01 01.11.26
Hanaoka
New
A-78550E
EDIT DATE DESIG.
DESCRIPTION
114/
316
TITLE
DRAW.NO.
3.8.5 (type)_TO_DINT
Function
When EN is set to ON and is receiving the power flow,
(type)_TO_DINT converts the data of input parameter IN to DINT data
and outputs the result to output parameter Q.
If the conversion results in an overflow, the maximum value for that
data type is output to Q. In such a case, ENO is not output.
Furthermore, if the conversion results in an underflow, the minimum
value for that type is output to Q. Again, in such a case, ENO is not
output.
(type)_TO_DINT instructions
Name Explanation
INT_TO_DINT Converts from INT to DINT
UINT_TO_DINT Converts from UINT to DINT
Format
(type)
TO
DINT
IN Q
(EN) (ENO)
??????? ???????
Parameters
Parameter Data type Meaning
EN BOOL Execution of conversion
IN INT, UINT Input data
ENO BOOL Normal end flag
Q DINT Result of conversion