B-63983EN/02 7.PMC DIAGNOSIS AND MAINTENANCE SCREENS ([PMC MAINTE])
- 753 -
In page 2 of the PARAMETER SETTING screen, you can set the
addresses or symbols that should be sampled.
Trace parameter setting screen (second page)
a) Setting addresses
In case of inputting discrete bit addresses, any bit address can be
inputted.
Moreover, when you input byte address, all bits of the address
(bits 0 to 7) are set automatically. Maximum 32 points of signal
address can be inputted.
With the multi-PMC system, an address can be set for a desired
PMC by specifying its PMC number.
Example: 2:R9200.1 + Input key
A setting can be made by entering "PMC number" + ":" +
"address" as indicated above.
When no PMC number is specified, the specification of the
currently selected PMC is assumed. In this case, "PMC number"
+ ":" is automatically prefixed to a specified address.
When only one PMC is used as in the standard PMC system, no
PMC number needs to be specified.