4. INTERFACE BETWEEN NC AND PMC
B–63505EN/02
168
1 Set to MDI mode or emergency stop state.
2 Set PARAMETER WRITE (on setting screen) to 1 or set the program
protect signal (KEY4) to 1.
Either one
Either one
PWE KEY4
Timer f –
Counter ff
Keep relay f –
Data table ff
3 Press a soft key and select a required screen.
[TIMER] :Timer screen
[COUNTR] :Counter screen
[KEEPRL] :Keep relay screen
[DATA] :Data table screen
4 Press cursor key and move the cursor to a desired number.
5 Input a numeric key and press
INPUT
key and data is input.
6 After the data is input, set PARAMETER WRITE or KEY4 on setting
screen to 0.
This screen is used for setting timer time of the functional instruction
(SUB 3).
PMC PARAMETER (TIMER) #001
TIMER
COUNTR KEEPRL
MONIT RUN
DATA
Page no. (screen is scrolled by page key)
NO.ADDRESS DATA
01 T00 480
02 T02 960
03 T04 0
04 T06 0
05 T08 0
06 T10 0
07 T12 0
08 T14 0
09 T16 0
10 T18 0
NO.ADDRESS DATA
11 T20 0
12 T22 0
13 T24 0
14 T26 0
15 T28 0
16 T30 0
17 T32 0
18 T34 0
19 T36 0
20 T38 0
Timer no. specified by functional instruction
Timer
delay
time
(msec)
Address specified by ladder
Timer set time : Timer no. 1–8 is max. 1572.8 sec and its accuracy is
48ms.
Timer no. 9 is max. 262.1 sec and its accuracy is 8ms.
4.3.5
PMCPRM Screen
D Inputting PMC
parameters from the MDI
D TIMER screen