B–63505EN/02
7.TROUBLESHOOTING
239
There are a plural interlock signals. Check at first which interlock signal
is used by the machine tool builder at the parameters shown below.
#7
3003
#6 #5 #4 #3
DIT
#2
ITX
#1 #0
ITL
#0 ITL=0 shows interlock signal *IT is effective. To 1)
#2 ITX=0 shows interlock signal *ITn is effective. To 2)
#3 DIT=0 shows interlock signal ± MITn is effective. To 3)
Check state of effective interlock signals using the diagnostic function
(PMCDGN) of the PMC.
1) Interlock signal (*IT) is input.
#7
G0008
#6 #5 #4 #3 #2 #1 #0
*IT
*IT=0 shows that interlock signal is input.
2) Axis interlock signal (*ITn) is input.
#7
G0130
#6 #5 #4 #3
*IT4
#2
*IT3
#1
*IT2
#0
+IT1
*ITn=0 shows interlock signal is input.
3) Interlock signal per axis and direction (± MITn) is input.
S M series
#7
G0132
#6 #5 #4 #3
+MIT4
#2
+MIT3
#1
+MIT2
#0
+MIT1
G0134 –MIT4 –MIT3 –MIT2 –MIT1
S T series
#7
X1004
#6 #5
–MIT2
#4
+MIT2
#3
–MIT1
#2
+MIT1
#1 #0
± MITn=1 shows interlock signal per axis and direction is input.
* For the T series, ± MITn is valid only for manual operation.
Check the signals using PMC’s diagnostic function (PMCDGN)
#7
*JV7G0010
#6
*JV6
#5
*JV5
#4
*JV4
#3
*JV3
#2
*JV2
#1
*JV1
#0
*JV0
*JV15G0011 *JV14 *JV13 *JV12 *JV11 *JV10 *JV9 *JV8
When the override is 0% all bits of the above address becomes
1111 1111 or 0000 0000.. . . . . . . . .
*JV15 JV0. . . . . . . . . . Override
1111 1111 1111 1111
1111 1111 1111 1110
:
1101 1000 1110 1111
:
0000 0000 0000 0001
0000 0000 0000 0000
0.00%
0.01%
:
100.00%
:
655.34%
0.00%
In this case, RESET is also displayed on the status display. Check it using
the procedure of 1 above.
b.Interlock or start lock
signal is input
c. Jog feedrate override is
0%
d.NC is in a reset state