B-64120EN/01 4.DESCRIPTION OF PARAMETERS
- 173 -
#7 #6 #5 #4 #3 #2 #1 #0
C07 C05 C04 C03 C02 C01
3406
C07 C05 C04 C03 C02 C01
#7 #6 #5 #4 #3 #2 #1 #0
C14 C11 C10 C08
3407
C15 C14 C13 C11 C10 C09 C08
#7 #6 #5 #4 #3 #2 #1 #0
C16
3408
C20 C19 C18 C17 C16
#7 #6 #5 #4 #3 #2 #1 #0
3409 CFH
[Data type] Bit
Cxx (xx: 01 to 20) When bit 6 (CLR) of parameter No.3402 is 1, the reset button on the
MDI panel, the external reset signal, the reset and rewind signal, or
emergency stop will,
0 : Clear the G code with group number xx.
1 : Not clear the G code with group number xx.
CFH When bit 6 (CLR) of parameter No.3402 is 1, the reset button on the
MDI panel, the external reset signal, the reset and rewind signal, or
emergency stop will,
0 : Clear F codes, H codes (for the M series), D codes (for the M
series), and T codes (for the T series).
1 : Not clear F codes, H codes (for the M series), D codes (for the M
series), and T codes (for the T series).
3410 Tolerance of arc radius
[Data type] 2-word
[Unit of data]
Input increment IS-A IS-B IS-C Unit
Millimeter input 0.01 0.001 0.0001 mm
Inch input 0.001 0.0001 0.00001 inch
[Valid data range] 1 to 99999999
When a circular interpolation command (G02, G03) is executed, the
tolerance for the radius between the start point and the end point is set.
If the difference of radii between the start point and the end point
exceeds the tolerance set here, a P/S alarm No.20 is informed.
NOTE
When the set value is 0, the difference of radii is
not checked.