4. DESCRIPTION OF PARAMETERS
B–63610EN/01
24
#7
0002
#6 #5 #4 #3 #2 #1 #0
RDG
[Data type] Bit
RDG Remote diagnosis is:
0: Not performed.
1: Performed.
If an RS–232C serial port is used to carry out remote diagnosis, connect
and set up the modem, cable, and the like, then set 1 in this parameter.
When using a modem card, the setting is not necessary.
#7
0201
#6
MCB
#5 #4 #3 #2
NCR
#1
ASC
#0
SB2
[Data type] Bit
SB2 The number of stop bits is
0: 1.
1: 2.
To carry out remote diagnosis, set 0.
ASC The code to be used for data output is:
0: ISO code.
1: ASCII code.
To carry out remote diagnosis, set 1.
NCR EOB (end of block) is output as:
0: ”LF””CR””CR”.
1: Just as ”LF”.
To carry out remote diagnosis, set 1.
MCB The baud rate setting for data input/output between the modem card and
CNC is:
0: 9600 bps (fixed).
1: Determined by the setting of parameter No. 203.
For the detailed setting while MCB is set to 1, see parameter No. 203.
4.4
PARAMETERS OF
REMOTE
DIAGNOSIS