B-65285EN/03 TROUBLESHOOTING 3.TROUBLESHOOTING AND ACTION
- 93 -
3.2.1 Alarm Code 1
(1) Meaning
Inverter: internal cooling fan stopped
(2) Cause and troubleshooting
(a) Check whether there is any foreign material in the fan.
(b) Be sure to push the faceplate (control printed-circuit board)
as far as it will go.
(c) Check that the fan connector is attached correctly.
(d) Replace the fan.
(e) Replace the SVM.
3.2.2 Alarm Code 2
(1) Meaning
Inverter: control power supply undervoltage
(2) Cause and troubleshooting
(a) Check the three-phase input voltage of the amplifier (the
voltage shall not be lower than 85% of the rated input
voltage).
(b) Check the 24 V power supply voltage output from the PSM
(the voltage shall normally not lower than 22.8 V).
(c) Check the connector and cable (CXA2A/B).
(d) Replace the SVM.
3.2.3 Alarm Code 5
(1) Meaning
Inverter: DC link undervoltage
(2) Cause and troubleshooting
(a) Check that the screws for the DC link connection cable (bar)
are tight.
(b) If a DC link low voltage alarm condition occurs in more than
one module, see Subsection 3.1.4, "Alarm code 4" for
explanations about how to troubleshoot the power supply
module.
(c) If a DC link low voltage alarm condition occurs in one SVM
only, be sure to push the faceplate (control printed-circuit
board) of that SVM as far as it will go.
(d) Replace the SVM in which this alarm has occurred.