4.CONFIRMATION OF THE OPERATION START-UP PROCEDURE B-65285EN/03
- 22 -
4.1.4 Checking Method when Magnetic Contactor Is not Switched
On
(1) The system is still in an emergency stop status.
→ Check the connection.
(2) There is a connector problem.
(a) Check that the connectors are attached to correct locations.
→ Ensure that the connectors are attached to the location
CXA2A on the PSM and the location CXA2B on the
SPM/SVM.
CXA2A
PSM
CXA2B
SPM/SVM
CXA2A
CXA2B
SPM/SVM
CXA2A
(Battery box for pulse coder)
(b) The interface cable between CXA2B of the power supply
module and CXA2A of the SVM or SPM is defective.
→ Check whether the interface cable is faulty.
(3) The power for driving the magnetic contactor is not supplied.
→ Check the voltage across the both ends of the coil of the
magnetic contactor.
(4) The relay for driving the magnetic contactor is defective.
→ Check that a circuit between pins CX3-1 and CX3-3 of
connector is closed and opened.
PSM
MCC driving relay
CX3-1
CX3-3
(5) The PSM, SVM, or SPM is defective.
→ Replace the defective module.