FANUC Series 16i/18i/21i-MB/TB,18i-MB5
Diagnosis screen for Dual Check Safety
Function Specifications
2002.11.19 T.Inagaki E.Genma
7/
14
A-78974E
02 030714 T.Inagaki (2) is altered
02 030714 T.Inagaki (2) is altered 02 030714 T.Inagaki (2) is altered
02 030714 T.Inagaki (2) is altered
Data display at the alarm occurrence
(1) General
[ 1 page ]
• The occurrence time, alarm number and message are displayed
when the first Dual Check Safety relation alarm is generated.
• Displaying “NO ALARM” on the time and “0” on all other data if
no Dual Check Safety alarm occurs.
• The alarm is displayed when one of the following alarm is occurs.
SV410, SV411, SV470-SV498
SP755/765/775/785-SP757/767/777/787
AL-69, AL-71, AL-72, AL-76, AL-77
• The factor of the safe function alarm is displayed when one of the
following alarm is occurs.
SV483, SV484, SV490, SP755/765/775/785
• The factor of the safe function alarm is displayed to PRM, PWO..
FM1 : Safety function is not executed is detected.
(flow monitoring alarm)
FM2 : Safety function is not executed is detected by another CPU.
(flow monitoring alarm)
CC1 : Safety function checking result does not matched with that of
another CPU. (cross check alarm)
CC2 : Sateth function checking result does not matched with that of
another CPU (cross check alarm)
CPU : Abnormality occurred with the self test of CPU.
RAM : Abnormality occurred with the RAM test.
PWO : Abnormality occurred with the self test at power ON.
PRM : Abnormality occurred with the safe parameter transfer.
• The flow counter and parameter number are displayed on
DATA1-4. (The display contents are changed by the alarm.)
• The DATA1-4 display relation alarm is as follows.
SV470-SV483, SV488, SV490, SV497, SP755, AL-76
In the case that the spindle software does not support this function,
“-“ is displayed.