Ethernet Re-recognition at start-up on Fanuc PANEL i Additional Manual Page 1

Additional Manual
TECHNICAL REPORT No. TMN 04/002E
Date . , 2004
General Manager of
CNC Laboratory
Ethernet Re-recognition at start-up on FANUC PANEL i
1. Communicate this report to:
Your information
O GE Fanuc-N, GE Fanuc-E
FANUC Robotics
CINCINNATI MILACRON
O Machine tool builder
Sales agency
End user
2. Summary for Sales Documents
3. Another Information
4. Attached Document
Drawing
No.
A-83136E Revision 01 (Total 3pages)
CC: CLB3 Rep.No. CLB3-04/1026
Date Jan.14,2004
Original section of issue
Vice General
Manager
Department
Manager
Section
Manager
Person in
Charge
FANUC
ADE

Contents Summary of Ethernet Re-recognition at start-up on Fanuc PANEL i Additional Manual

  • Page 1TECHNICAL REPORT No. TMN 04/002E Date . , 2004 General Manager of CNC Laboratory Ethernet Re-recognition at start-up on FANUC PANEL i 1. Communicate this report to: Your information O GE Fanuc-N, GE Fanuc-E FANUC Robotics CINCINNATI MILACRON O Machine tool builder Sales agency End user 2. Summary fo
  • Page 2Ethernet Re-recognition at start-up on FANUC PANEL i 1. OUTLINE This document describes the phenomenon and countermeasure about Ethernet re-recognition on FANUC PANEL i with Celeron 733MHz / Pentium III 866MHz / Pentium III 1.26GHz CPU when Windows 2000 Professional (We call it “Windows 2000” after
  • Page 34. CAUSE EEPROM which is used in PANEL i master circuit board as MAC address storage was discontinued. Therefore, we changed it to the new EEPROM. When PANEL i with the master circuit board mounted the new EEPROM is start up with connecting to the HDD which current OS image is pre-installed, OS reco
  • Page 4B) When the following message is appeared on the screen, enter ‘C:\WINNT\system32\drivers’ on [Copy files from] box, then press [OK] button. C) When the following message is appeared on the screen, enter ‘C:\WINNT\system32’ on [Copy files from] box, then press [Retry] button. D) Wait until the follo