6.HEAT DISSIPATION A-72562EN-027
- 56 -
(2) Residual amount of heat in the cabinet
By placing the heat sink section of the SVM outside the cabinet,
the residual amount of heat in the cabinet can be calculated
according to the expression below.
Residual amount of heat in the cabinet
=a + Ka1 x b1 + Ka2 x b2 + Ka3 x b3+ Ka4 x b4+Ka5 x b5
a : Amount of heat dissipation determined by the SVM
model [W]
Ka1~ Ka5: Coefficient determined by the SVPM
b1 : Total output og the motors connected the SVPM [kW]
b2 : Current flowing through the spindle motor [Arms]
b3 : Current flowing through the servo motor of L axis [Arms]
b4 : Current flowing through the servo motor of M axis [Arms]
b5 : Current flowing through the servo motor of N axis [Arms]
SVPM
Name Specification
a
[W]
K
[W/Arms]
Ka1 2.1
Ka2 0.9
Ka3 0.8
SVPM2-5.5i
H201 22
Ka4 0.8
Ka1 2.1
Ka2 0.8
Ka3 0.8
SVPM2-11i
H202 22
Ka4 0.8
Ka1 1.3
Ka2 0.6
Ka3 0.5
SVPM2-15i
H203 22
Ka4 0.5