2.CABLE CONNECTION CONNECTION B-64164EN/01
- 126 -
NOTE
1 The ground between PC/HUB side and machine
system side must be separated. If it is impossible
to separate the ground because there is only one
grounding point, connect the ground cable for each
system to the grounding point independently. (See
figure below.)
The resistance for grounding must be less than
100-ohm (Class D). The thickness of the ground
cable is the same as the thickness of AC power
cable or more. At least thickness of 5.5mm
2
is
necessary.
2 Note that the number of allowable hub-to-hub
connections depends on the type of hub.
3 There is possibility that noise makes the obstacle
of communication even if the ground is separated
using the 10BASE-T. In the case of using the
FL-net board under the worst environment, please
separate between the PC/Trunk line side and
machine system side completely using the
10BASE-FL (Optical fiber media).
HUB
FG
Ground wire on personal
computer and trunk sides
Ground wire on machine system
FG
Ground point
Note 2
Ground wire on
machine system
Wiring on a single ground point