B–64113EN/01
3. INSTALLATION
19
Table 3.4.3 (a) Heat output
Unit
0i
0i
Mate
Heat
output
(W)
Remarks
Control unit
Without option slots f f 33W (*1)
With 2 option slots f — 37W (*1)
Option board
HSSB board f — 3W
(*2)
Serial communication
board (DNC2)
f — 6W
Data server board f — 9W
NOTE
1 The liquid–crystal display and MDI unit are included. Option
boards are not included.
2 When option boards are used, the total heat output of the
selected option boards must not exceed the following value:
Rack type Total heat output
2–slot rack 26W
Table 3.4.3 (b) Heat output
Unit Heat output (W) Remarks
MDI unit 0W
Operator’s panel I/O module 12W (*1)
Connector panel I/O module (basic) 8W (*1)
Connector panel I/O module (additional) 5W (*1)
I/O unit for 0i (*1)
Separate detector interface unit 9W Basic 4–axis unit only(*2)
NOTE
1 The indicated values are when 50% of the module input
signals are ON.
2 Heat output generated within the separate detector is not
included.
3.4.3
Heat Output of Each
Unit