3. Parameters
#7 #6 #5 #4 #3 #2 #1 #0
4399 CTLSTP
[Data type] Bit spindle axis
CTLSTP In dual check safety function, when the exceeding spindle safety speed alarm
occurs,:
0 : The controlled stop function is disabled.
1 : The controlled stop function is enable. (controlled stop and power-down after zero
speed detection signal SST becomes “1”.)
Note1) When CTLSTP is “1”, MCC off timer (No.1947 / No.1948) is valid if the exceeding
spindle safety speed alarm occurs. Set the parameter No.1947/No.1948 in order to
wait MCC off until the spindle stops.
Note2) When CTLSTP is “1”, if the spindle software detects the acceleration of the spindle
during the controlled stop, the power is shut down and the spindle freely rotates.
1947 MCC off timer 1 (If the protective door is closed)
1948 MCC off timer 2 (If the protective door is opened)
[Data type] Word
[Unit of Data] ms
[Valid data range] 0 to 32767
In dual check safety function, set the parameter No.1947 / No.1948 in order to wait
MCC off until the spindle stops.
Note) If the spindle alarm occurs, MCC off timer 1 / 2 (No.1947 / No.1948) are not used
when the parameter No.4399#1 (CTLSTP) is “0”. However, when the parameter
No.4399#1 (CTLSTP) is “1”, MCC off timer 1 / 2 are effective in the case of the
exceeding spindle safety speed alarm.
Edit
Apprv.
Desig.
Sheet
TITLE
Draw
No.
Date
Design
Descri
tion
Date
FANUC Series 16i/18i/21i - B, 18i - MB
Dual Check Safety Spindle Controlled Stop at
Exceeding Safe Speed Specifications
A-90080E
2005.05.31 M.Ito
3
4