A-90188E-01 SETTING 1.MODBUS/TCP SERVER FUNCTION
- 21 -
Setting item
Item Description Parameter No
BASIC
PORT NUMBER
(TCP)
Specify the port number to be used by the
MODBUS/TCP Server function.
The available range is form 0 to 65535.
The default listening port number is 502.
Pa20
Specify PMC address to set MODBUS status.
If the status information is not necessary, specify a
space character (SP).
The available PMC area is %M and %ME.
For a PMC address %M or %ME:
The available range is from %M1 to %M63993.
But the PMC adress number (1-63993) has to be
satisfied the following condition.
Condition) (8*n)+1 [n = 0 - 7999]
STATUS PMC
ADDRESS
Example) "M1", "M9", "M17", - - - "M63993"
Pa21
AREA1-3
COMMUNICATE Choose whether AREA1 is used as I/O area of
MODBUS or not.
DISABLE : Not used
ENABLE : Used
AREA1:Pa30
AREA2:Pa40
AREA3:Pa50
Specify the start address of the PMC area which is
used to exchange I/O data with MODBUS/TCP
clients.
If you do not want to set this address, specify a
space character (SP).
The available PMC area is %M, %ME and %R.
According to each PMC area, a range is the
following.
For a PMC address %M or %ME:
The available range is from %M1 to %M63985.
But the PMC adress number (1-63985) has to be
satisfied the following condition.
Condition) (8*n)+1 [The even of n = 0 - 7999]
Example) "M1", "M17", "M33", - - - "M63985"
For a PMC address %R:
The available range is from %R1 to %R5000.
DATA PMC
ADDRESS
Example) "R1", "R2", "R3", - - - "R5000"
AREA1:Pa31
AREA2:Pa41
AREA3:Pa51
DATA MODBUS
ADDRESS
Specify the start address of the MODBUS area
(Holding Registers) which is used to exchange I/O
data with MODBUS/TCP clients.
The available range is from 0 to 65534.
AREA1:Pa32
AREA2:Pa42
AREA3:Pa52