A-79364E
Title
Draw
No.
Ed. Date Design Description
Date Jan.07.’04 Design. Apprv.
11/13
Page
FANUC Series 30i-MODEL A
Linear scale with distance-coded
reference marks
serial
[The setting method of parameter No.1883]
You can determine the setting value by the following procedure.
(1) Set "1" to parameter No.1815#2,#1, No.1818#3 to make this function
available.
Set a correct value to parameter No.1821, No.1882.
Set "0" to parameter No.1240.
Set "0" to parameter No.1883,1884.
(2) Establish a reference point by the procedure described in "procedure for
reference position establishment".
(As a result, the machine coordinate becomes the distance between
scale zero and actual position.)
(3) Positioning the axis to reference position by mechanical measurement
in "HND" or "JOG" mode.
(4) Set an actual machine coordinate value to the parameter No.1883 after
conversion of least command increment to detection unit.
(5) Set a parameter No.1240 if necessary.
Note
1. Set the valid range, within –999,9999,999,999 to
+999,9999,999,999 for setting parameter No.1883,
1884.
If setting value is over the valid range, the alarm
PS5325 occurs.
2. It is not available to cross the scale zero under s
cale valid area of the linear scale with distance-c
oded reference marks (serial).
Please adjust the scale valid area which the scal
e zero is located within the next scale zero is val
id.
14010
Allowable move amount of FL feedrate on establishment of reference
point(linear scale with distance-coded reference marks (serial))
[Input type] Parameter input
[Data type] 2-word axis
[Unit of data] Detection unit
[Valid data range] -999999999 to 999999999