FANUC Series 30i-MODEL A
Distance coded linear scale interface
FEED AXIS SYNCHRONIZATION CONTROL
Requirements when this function is used with feed
axis synchronization control axes
When this function is used with feed axis synchronization control axes, the
distance coded linear scale used for the master axis and that used for the
slave axis must have reference marks placed at identical intervals.
(Set identical values in parameter Nos. 1821 and 1882 for both the
master and slave axes.)
This function does not work unless the use of this function is specified
for both the master and slave axes (bit 7 (DCL) of parameter No. 1815 is 1).
Also, in all parameters related to this function, except parameter No. 1883,
1884 (distance from the scale zero point to reference position 1, 2), set
identical values for both the master and slave axes.
If a parameter value for the master axis differs from the corresponding
parameter value for the slave axis, alarm SV1051 is issued.
Note
1. When this function is used with feed axis synchronization
control axes for which the operation mode is switched
between synchronization operation and normal operation,
this function is enabled only if the synchronization select
signal (SYNC1, SYNC2, ...) is 1. (During establishment of
a reference position, the synchronization select signal
status must be maintained.)
Reference position establishment with feed axis
synchronization control axes
With feed axis synchronization control axes, a reference position is
established as follows. When a reference mark for the master or slave axis is
detected, a stop takes place temporarily. Then, a feed operation is performed
again at the reference position return FL feedrate. This sequence is repeated
until a reference mark is detected three or four times for both the master and
slave axes. Then the absolute position is calculated for both the master and
slave axes, and the reference position establish signals (ZRF1, ZRF2, ...) are
set to 1.
After the reference position has been established by the above operation, a
synchronization error is corrected. (Checking for excessive synchronization
error alarm 2 is made even during reference position establishment.)