B–63083EN/02
9. CONNECTION TO FANUC I/O Link
173
Fixed addresses directly supervised by the CNC (for FS21i/210i)
7 6 5 4 3 2 1 0
SKIP ESKIP –MIT2 +MIT2 –MIT1 +MIT1 ZAE XAE
X0004 SKIP6 SKIP5 SKIP4 SKIP3 SKIP2 SKIP8 SKIP7
SKIP ESKIP SKIP5 SKIP4 SKIP3 ZAE YAE XAE
SKIP6 SKIP2 SKIP8 SKIP7
X0005
X0006
X0007
X0008 *ESP
X0009 *DEC4 *DEC3 *DEC2 *DEC1
The upper row indicates those signals used for the T series. Those in the
lower row are for the M series.
X0008
X0009
X0010
X0011
X0012
X0013
X0014
X0015
X0016
X0017
X0018
X0019
X0020(for 1st MPG)
X0021(for 2nd MPG)
X0022(for 3rd MPG)
X0023(DO alarm
detection)
MPG
When DI addresses are allocated in units of 16 bytes, starting at X0008
General–purpose
input signal
Reserved
Matrix input
signal
Reserved
DO alarm
detection
Although fixed signals such as SKIP cannot be used,
allocating DI addresses starting from X0008 allows the *DECn
signal to be used and the *ESP fixed signal to be allocated to
an address for which the common voltage is fixed to 24 V.
(Fixed signals cannot be allocated to the for the matrix input
signals.)
*ESP fixed signal
*DECn fixed signal
All the DO signals can be turned off simultaneously by turning off
(opening) the DO (output signal) power supply pin “DOCOM”. Doing
so causes the DO signal status to change as shown below.
DOCOM
ON
OFF
ON
OFF
ON
OFF
When DO is ON in
the sequence
When DO is OFF
in the sequence
Turning the DO (output
signal) power on and off
(DOCOM)