B-63323EN-1/03 1.AXIS CONTROL
- 209 -
7799 Limit value for synchronization error check based on
position deviation
[Input type] Parameter input
[Data type] Integeraxis
[Unit of data] detection unit
[Valid data range] 0 - 999999999
Alarm OT513 is issued if the absolute positional deviation difference
between the master axis and slave axis during synchronization control
exceeds the value specified in this parameter.
Set a desired value for the slave axis.
When 0 is set in this parameter, no check is made.
Notice related to axis-type parameter setting
Axis-type parameters for axes controlled in synchronization are
grouped into the following four categories:
(1) Parameters in which the same data must be set for both the master
axis and slave axis.
(2) Parameters in which data must be set only for the master axis (data
for the slave axis is not used).
(3) Parameters in which the data to be set may differ between the
master axis and slave axis.
(4) Parameters in which data must be set only for the slave axis (data
for the master axis is not used).
The category of each parameter is explained below. If the category of a
parameter is unknown, assume it to be in category (1), and set the
parameter with the same data for both the master axis and slave axis.
CAUTION
1 If different values are set in a type (1) parameter for
the master axis and slave axis, the axes may fail to
operate under synchronization control normally.
2 If the master and slave axis use different types of
motors or detectors, the type (1) parameters
indicated by *1 must be specified for individual axes
separately.
3 If a signal is used to switch between synchronous
operation and normal operation, type (2) parameters
must also be specified for the master axis and the
slave axis separately.