APPENDIXG. ALARM LIST
B–64134EN/01
752
Number ContentsMessage
463 n AXIS : SEND SLAVE DATA
FAILED
Because of an FSSB communication error, the servo system could not
receive correct data.
464 n AXIS : WRITE ID DATA FAILED An attempt was made to write maintenance information on the amplifier
maintenance screen, but it failed.
465 n AXIS : READ ID DATA FAILED At power–up, amplifier initial ID information could not be read.
466 n AXIS : MOTOR/AMP
COMBINATION
The maximum current rating for the amplifier does not match that for the
motor.
467 n AXIS : ILLEGAL SETTING OF
AXIS
The servo function for the following has not been enabled when an axis
occupying a single DSP (corresponding to two ordinary axes) is speci-
fied on the axis setting screen.
1. High–speed current loop (bit 0 of parameter No. 2004 = 1)
2. High–speed interface axis (bit 4 of parameter No. 2005 = 1)
468 n AXIS : HI HRV SETTING ERROR
(AMP)
This alarm is issued if it is specified that high–speed HRV control is to
be used for a controlled axis connected to an amplifier for which high–
speed HRV control cannot be used.
The details of servo alarm are displayed in the diagnosis display (No. 200
and No.204) as shown below.
#7
OVL200
#6
LV
#5
OVC
#4
HCA
#3
HVA
#2
DCA
#1
FBA
#0
OFA
#7 (OVL) : An overload alarm is being generated.
#6 (LV) : A low voltage alarm is being generated in servo amp.
#5 (OVC) : A overcurrent alarm is being generated inside of digital servo.
#4 (HCA) : An abnormal current alarm is being generated in servo amp.
#3 (HVA) : An overvoltage alarm is being generated in servo amp.
#2 (DCA) : A regenerative discharge circuit alarm is being generated in servo amp.
#1 (FBA) : A disconnection alarm is being generated.
#0 (OFA) : An overflow alarm is being generated inside of digital servo.
#7
ALD201
#6 #5 #4
EXP
#3 #2 #1 #0
When OVL equal 1 in diagnostic data No.200 (servo alarm No. 400 is
being generated):
#7 (ALD) 0 : Motor overheating
1 : Amplifier overheating
When FBAL equal 1 in diagnostic data No.200 (servo alarm No. 416 is
being generated):
ALD EXP Alarm details
1 0 Built–in pulse coder disconnection (hardware)
1 1 Separately installed pulse coder disconnection
(hardware)
0 0 Pulse coder is not connected due to software.
D Details of servo alarm