9. TEMPERATURE INPUT MODULE CONNECTIONS B-61813E/03
−100−
9.2 TEMPERATURE INPUT MODULE SPECIFICATION
Input signal types and
number of input
channels
• Types ATI04A
Three-wire thermoresistance (JPt100Ω)
Three-wire thermoresistance (Pt100Ω)
ATI04B
J thermocouple (can also be used with
the tip grounded)
K thermocouple (can also be used with
the tip grounded)
• Number of input channels
2/4, for all for which the input is the same
Input signal switching
method
• User program (ladder)
Temperature
measurement range
and precision
• Thermoresistance type (ATI04A)
-50 to 300.0°C
Resolution 0.1°C
Overall precision ±1%FS
• Thermocouple type (ATI04B)
0 to 600.0°C
Resolution 0.1°C
Overall precision ±1%FS
Data sampling period
setting (NOTE)
• 0.3 s per two channels
• 0.5 s per four channels to 10 s per four channels
(4 s per four channels is assumed if no specification is
made)
System failure check • Self-diagnosis
A watchdog timer is used.
• Abnormal temperature (including sensor input
disconnection)
Failure information about each abnormal channel
is sent to the PMC.
Interface with the PMC • PMC → temperature module
Information format: Binary or bit
Signals: 32 points
• Temperature module → PMC
Information format: Binary or bit
Signals: 32 points
External connection Connector
(Hirose Electric Co., Ltd.: HIF3BA-34PA-2.54DS)
NOTE
The actual response time is the sum of the time
required for the signal to pass the filter and the scan
time that is determined depending on the system1