G. FSSB START--UP PROCEDURE/
MATERIALS
B--63005EN/02
APPENDIX
814
D AXIS NO: Controlled axis number
The NC controlled axis numbers are displayed sequentially.
D NAME: Controlled axis name
D AMP: Type of amplifier connected to each axis
D M1: Connector number for pulse module 1
The connector number for pulse module 1 set in parameter No. 1931
is displayed.
D M2: Connector number for pulse module 2
The connector number for pulse module 2 set in parameter No. 1932
is displayed.
D 1DSP
The value set in bit 0 (1DSP) of parameter No. 1904 is displayed. The
value 1 is displayed for an axis (leaning control axis, high--speed
current loop axis, high--speed interface axis) that exclusively uses a
DSP.
D CS: Cs contour control axis
The value set in parameter No. 1933 is displayed. The value 1 is
displayed for a Cs contour control axis.
D TANDEM (M series only)
The value set in parameter No. 1934 is displayed. For a master axis
and slave axis used for tandem control, an odd number and a
subsequent even number are displayed.
The amplifier maintenance screen displays servo amplifier maintenance
information. There are two types of amplifier maintenance screens as
shown below. The user can switch between the two screens with the page
keys
and .
(AMPLIFIER SETTING) O1000 N00001
1 X A1-L ∼ SVM-HV 2 40AL
2 Y A1-M ∼ SVM 2 12A
3 Z A2-L ϒ SVM 1 40A
4 A A3-L ∼ SVM 2 20A
5 B A3-M ∼ SVM 2 40A
6 C A4-L ∼ SVU 1 240A
MDI **** *** *** 13:11:56
[ AMP ][ AXIS ][ MAINT ][ ][ (OPRT) ]
G.9.3
Amplifier Maintenance
Screen