4. DIGITAL SERVO
B–63465EN/01
78
S When a three–axis amplifier is used, the requirement for a two–axes
amplifier described above applies to the first and second axes, and the
requirement for a one–axis amplifier, again described above, applies to
the third axis.
S When an odd number is specified for parameter No.1023, the fast type
interface must be used.
S When an even number is specified for parameter No.1023, only the
slow type interface can be used. (The FSL bit must always be set to 1.)
Controlled
axis
number
1
2
3
4
5
6
Program
axis name
No.1020
X
Y
Z
A
B
C
Servo axis
number
No.1023
1
2
3
4
5
6
Interface
type
Fast/Slow
F
F
S
S
F
S
Digital Servo Adapter
2–axis
amplifier
2–axis
amplifier
1–axis
amplifier
X (Fast)
A (Slow)
Y (Fast)
Z (Slow)
B (Fast)
C (Slow)
1–axis
amplifier
PM1 The first pulse module is:
0 : Not used.
1 : Used.
PM2 The second pulse module is:
0 : Not used.
1 : Used.
NOTE
When manual setting 2 mode is selected for FSSB setting
(when the FMD parameter (bit 0 of parameter No.1902) is
set to 1), parameter No.1905 must be set directly. When a
pulse module is used, a connector number must be set in
the corresponding parameter (No.1936 or No.1937).