2. CONNECTION
B–62443EN–2/03
30
[Classification] Contact signal input used for emergency stop, tied to
common 24 V
[Function] The emergency stop input signal stops the loader
immediately in situations such as loader overtravel
(detected by hardware) or hand destruction. B
contact point input is assumed. So, ensure that 24 V
is applied in the normal state. When this DI signal is
read in the normal state, a value of 1 is read. When
this signal is turned off (when the contact opens), this
DI signal changes to 0, and the *EMG1 signal of the
CNPW connector is turned off. Then, the externally
mounted emergency stop control relay is turned off
to shut down the MCC of the servo system. This
shutdown state continues for as long as *LOT is off.
To enable this state to be released temporarily, the
OTR signal is provided. See Section 2.6 for further
information.
[Classification] Contact signal input, switchable between common
24 V and 0 V
[Function] For workpiece feeder interfacing, 8 input signals are
provided. These signals can also be used for general
purpose applications, depending on the function
demanded of the mechanical unit of the loader.
However the skip function is used, FDI08 is used as
skip signal. Skip operation is no required, FDI08 can
be used for general applications. These signals are
also applied to a separate connector, CNWF,
connected in parallel.
[Classification] Common voltage selection
[Function] When COMWF is connected to 0V, FDI01 to FDI08
function as 24 V common voltage input signals.
When COMWF is connected to +24E, FDI01 to
FDI08 function as 0 V common voltage input
signals. Note that the signal polarity also changes
accordingly. That is, when FDI01 to FDI08 are
functioning as 24 V common voltage signals, logic
1 corresponds to the contact being closed; when
FDI01 to FDI08 are functioning as 0 V common
voltage signals, logic 0 corresponds to the contact
being closed. This signal is also applied to a separate
connector, CNWF, connected in parallel.
[Classification] Transistor sink output, 24 V/200 mA load
[Function] For workpiece feeder interfacing, 8 output signals are
provided. These signals can also be used for general
purpose applications, depending on the function
demanded of the mechanical unit of the loader. These
signals are also applied to a separate connector,
CNWF, connected in parallel.
Loader overtravel signal
*LOT
General–purpose
workpiece feeder input
signals
FDI01 to FDI08
General–purpose input
signal common voltage
selection for the
workpiece feeder
COMWF
General–purpose
workpiece feeder output
signals
FDO01 to FDO08