4.SEPARATED REGENERATIVE DISCHARGE UNIT FANUC AC SERVO AMPLIFIER β series B-65232EN/03
- 150 -
4.1 FOR SVU-4, SVU-12, AND SVU-20
4.1.1 Cases Where a Separated Regenerative Discharge Unit Is Not
Required
When the amount of regenerative energy produced [J] never exceeds
the amounts indicated in Table 4.1, a separated regenerative discharge
unit is not required.
For an external connection to be made when a regenerative
discharge unit is not used, see Part V, "CONNECTION", of this
manual.
An incorrect connection can damage the amplifier. Care must be
taken.
Table 4.1 Maximum allowable regenerative energy for amplifiers
Name Maximum allowable regenerative energy
SVU-12 13 [J]
SVU-20 16 [J]
Calculating the amount of regenerative energy produced
- For horizontal operation
(a) When the SI unit system is used
)( ][)1023.5)(1048.5( 1 Expression
2
23
JTLVmtaVmJLJmP ⋅⋅⋅×−⋅+⋅×=
−
−
Jm: Motor rotor inertia [kg⋅m
2
]
JL: Load inertia converted to motor shaft inertia [kg⋅m
2
]
Vm: Motor speed during rapid traverse [min
-1
]
ta: Acceleration/deceleration duration during rapid traverse
[sec]
TL: Machine tool friction torque (in terms of motor) [N⋅m]
(b) When the CGS unit system is used
)( ][)1013.5)(1037.5( 1 Expression
324
JTLVmtaVmJLJmP ⋅⋅⋅×−⋅+⋅×=
−−
Jm: Motor rotor inertia [kgf⋅cm⋅sec
2
]
JL: Load inertia converted to motor shaft inertia [kgf⋅cm⋅sec
2
]
Vm: Motor speed during rapid traverse [min
-1
]
ta: Acceleration/deceleration duration during rapid traverse
[sec]
TL: Machine tool friction torque (in terms of motor) [kg⋅cm]