B-65232EN/03 CONNECTION 11.EXTERNAL PULSE INPUT (ONLY FOR I/O Link INTERFACE)
- 295 -
11.2 CONNECTION WHEN A MANUAL PULSE GENERATOR
AVAILABLE FROM FANUC IS USED
11.2.1 K23 Cable Connection
The K23 cable is a signal cable for connecting a manual pulse
generator with a manual pulse generator adapter (JA54).
Connector : FI40-2015S
Case : FI-20-CV
(M3 screw terminal)
+5V 0V A B
+5V 0V HA1 HB1
Manual pulse generator
Manual pulse generator adapter
K23
Cable connection(K23)
HA1
HB1
+5V
0V
A
B
+5V
0V
HA1
HB1
+5V
0V
Shield
JA54
(PCR-EV20MDT)
1HA111
2 HB1 12 0V
3(HA2)13
4 (HB2) 14 0V
515
6160V
717
818+5V
9 +5V 19
10 20 +5V
Manual pulse generator
1
2
9,18,20
12,14,16
JA54
#24AWG
#20AWG
Recommended wire : A66L-0001-0286 (#20AWG × 6 + #24AWG ×
3 pairs)
Recommended connector (on the JA54 side): A02B-0120-K303
Recommended cable : A02B-0259-K821 (7 m). When using the cable,
rewrite the connector name.
The maximum allowable length is 50 m. However, another limitation
based on a power supply voltage drop is imposed as described below.
Limitation based on a power supply voltage drop
Suppress the power supply voltage drop due to cable resistance to 0.2
V or less (sum of the 0V and 5V lines).