9.FANUC I/O Link CONNECTION (FOR I/O Link INTERFACE ONLY) CONNECTION B-65232EN/03
- 286 -
A66L-0001-0284#10P (10 twisted pair cable with a shield on the
outside)
NOTE
1 Maximum cable length: 10 m (when the above
recommended wire is used)
2 Use the same twisted wire pair for the SIN and *SIN
signals. Also use the same twisted wire pair for the
SOUT and *SOUT signals.
3 Do not make any connection to the pins other than
those shown above. Do not connect an unused
conductor of the cable.
4 Connect the shield of the cable to the ground plate
of the cabinet by using a cable clamp. Regardless
of whether a β series servo amplifier is connected
with the host controller (or the slave unit at the
previous stage) or the slave unit at the next stage,
clamp and shield the cable immediately when the
cable is run into the cabinet. If the host controller is
installed in one cabinet, and a β series servo
amplifier is installed in another cabinet, shield
processing is required twice for one cable. Even if
the cable is not routed outside the cabinet, be sure
to clamp and shield the cable at least one location.
5 Switch on the control power for the servo amplifier
at the same time with or before the host controller
connected to the servo amplifier through the I/O
Link. When switching off the host controller power,
also switch off the servo amplifier control power.
Host controller ON
power OFF
Servo amplifier ON
control power OFF
t : 0 or more
t