(5) Alarm messages (For EDIT: PMC–SB7)
Messages displayed during update of the PMC ladder diagram editing
Alarm number Faulty location/corrective action Contents
OVERLAPPED COM If COME is missing, add it in proper posi-
tion. If the COM is unnecessary, remove it.
There is no COME that corresponds to
this COM.
END IN COM
END1 IN COM
END2 IN COM
If COME is missing, add it in proper posi-
tion. If COM is unnecessary, remove it.
END,END1,END2, or END3 is found be-
tween COM and COME.
JMPE IN COM JMPE and corresponding JMP must have
same COM/COME status. Review JMP
range and COM range, to adjust not to
overlap with each other: it is possible that
one range includes the other completely.
JMPE is found between COM and
COME, and JMP and corresponding
JMPE have different COM/COME status.
SP/SPE IN COM If COME is missing, add it in proper posi-
tion. If the COM is unnecessary, remove it.
SP or SPE is found between COM and
COME.
COME WITHOUT COM If COM is missing, add it in proper position.
If the COME is unnecessary, remove it.
There is no COM that corresponds to this
COME.
DUPLICATE CTR NUMBER
(WARNING)
If some of them are unnecessary, remove
them. If all of them are necessary, assign
other number to parameter of them to
make them unique. (If two or more instruc-
tions with same parameter number will
never be active simultaneously at one
time, the Ladder program has a possibility
to work correctly, however, it is recom-
mended from safety and maintenance
points of view, that all these instructions
should have different parameter number
with each other.)
Plural CTRs have the same number as
their parameter.
(This is warning.)
ILLEGAL CTR NUMBER If unnecessary, remove it. Assign correct
number not to exceed the maximum num-
ber defined by each PMC model.
CTR has parameter number that is out of
range.
DUPLICATE DIFU/DIFD NUM-
BER (WARNING)
If some of them are unnecessary, remove
them. If all of them are necessary, assign
other number to parameter of them to
make them unique. (If two or more instruc-
tions with same parameter number will
never be active simultaneously at one
time, the Ladder program has a possibility
to work correctly, however, it is recom-
mended from safety and maintenance
points of view, that all these instructions
should have different parameter number
with each other.)
Plural DIFUs or DIFDs have the same
number as their parameter.
(This is warning.)
ILLEGAL DIFU/DIFD NUMBER If unnecessary, remove it. Assign correct
number not to exceed the maximum num-
ber defined by each PMC model.
DIFU or DIFD has parameter number
that is out of range.
NO END
NO END1
NO END2
NO END3
Add END, END1, END2 or END3 in proper
position.
END, END1, END2 or END3 is not
found.
APPENDIX
GFKE-0222-EN
A. ALARM LIST
889