3. PERIPHERAL EQUIPMENT CONTROL
B--65245EN/02
HANDLING
102
#7 #6 #5 #4 #3 #2 #1 #0
005 ABSPS LDM
Size : 1 byte/bit type
Standard value :0
ABSPS With the response data read function, the host and servo
amplifier unit are:
0 : Not synchronized.
1 : Synchronized. (Even during m ovement on axes, the
host can read correct position data.)
LDM Motor current value output in response data (Xx+3 to
Xx+6) is:
0 : Disabled.
1:Enabled.
020 Specification of the contents of response data (PHOUT)
Size : 1 byte
Standard value :3
PHOUT As response data (Xx+3 to Xx+6):
0 : No data is output.
1 : ATC or point number data is output. In the case of
ATC cycle or point positioning:
2 : Machine coordinates are output.
3 : Workpiece coordinates are output.
4 : A motor current value is output. The motor current
value 6554 represents the maximum current value of
the servo amplifier unit.
NOTE
For output of a motor current value as response data, set bit
6 (LDM) of parameter No. 005 to 1, and set parameter No.
020 to 4.