Edit.
13/13
Date Signature Change
FANUC SERVO MOTOR BETA series I/O
Link Option Add function in edition 09
B-65245EN/02-01
Related parameter
Related parameterRelated parameter
Related parameter
No
020 Response data specifications (PHOUT)
Size
SizeSize
Size : 1 byte
Standard value
Standard valueStandard value
Standard value : 3
PHOUT
PHOUTPHOUT
PHOUT Specifies what to output as response data (Xx+3 to Xx+6), as
follows:
0 : Nothing is output.
1 : An ATC and point No. are output if an ATC cycle and point
positioning are performed.
2 : The machine coordinate is output in real time.
3 : The workpiece coordinate is output in real time.
4 : The current value of motor is output.
The motor current value 6554 means the maximum value of the
amplifier.
NOTE
When the motor current value is selected as response data, the parameter No.005#6
(LDM) must be set to “1” and the parameter No.020 must be set to “4”.
7.3.
7.3.7.3.
7.3.
Note
Note Note
Note
When the parameter No.007#2(NZPRO) is set to “1” and the incremental pulse-coder is used, the
coordinate setting must be done in order to establish the relation between the machine and the
coordinate, before the ATC cycle or the point positioning is performed. If the ATC cycle or the point
positioning is performed before the coordinate setting, there is a possibility not to position to the
correct machine position. And the turret and magazine number or the point number in this case may
be incorrect.
The above caution is applied to all of the positioning motion besides the ATC cycle or the point
positioning.