APPENDIX
B–62755EN/01
B. ALARM LIST
447
(1) Alarm messages (PMC)
Message Contents and solution
ALARM NOTHING Normal status
ER00 PROGRAM DATA
ERROR(ROM)
The sequence program in the ROM is not written correctly.
(solution) Please exchange ROM for the sequence program.
ER01 PROGRAM DATA
ERROR(RAM)
The sequence program in the debugging RAM is defective.
(solution) Please clear the debugging RAM and input LADDER again.
The debugging RAM is not installed though the RAM is selected.
(solution) Please install the debugging RAM or install ROM for sequence program
and select ROM with K17#3=0.
ER02 PROGRAM SIZE OVER The size of sequence program exceeds the maximum size of LADDER(PMC–RC only).
(solution) Please change MAX LADDER AREA SIZE at the SYSPRM screen and
restart the system.
ER03 PROGRAM SIZE
ERROR(OPTION)
The size of sequence program exceeds the option specification size.
(solution) Please increase the option specification size.
Or, reduce the size of sequence program.
ER04 PMC TYPE UNMATCH The PMC model setting of the sequence program is not corresponding to an actual mod-
el.
(solution) Please change the PMC model setting by the offline programmer.
ER05 PMC MODULE TYPE
ERROR
The module type of the PMC engine is not correct.
(solution) Please exchange the module of PMC engine for a correct one.
ER06 PROGRAM MODULE
NOTHING
Both ROM for sequence program and the debugging RAM do not exist (PMC–RC only)
ER07 NO OPTION
(LADDER STEP)
There is no step number option of LADDER.
ER 16 RAM CHECK ERROR
(PROGRAM RAM)
The debugging RAM cannot be read/written normally.
(solution) Please exchange the debugging RAM.
ER17 PROGRAM PARITY The parity error occurred on ROM for sequence program or the debugging RAM.
(solution) ROM: The deterioration of ROM may be deteriorated
Please exchange ROM for the sequence program
RAM: Please edit the sequence program once on PMC
Still the error occurs, exchange the debugging RAM.
ER18 PROGRAM DATA ERROR
BY I/O
Transferring the sequence program from offline programmer was interrupted by the
power off etc.
(solution) Please clear the sequence program and transfer the sequence program
again.
ER19 LADDER DATA ERROR Editing the LADDER was interrupted by the power off or by the switch to the CNC screen
by the function key etc.
(solution) Please edit LADDER once on PMC.
Or, please input LADDER again.
ER20 SYMBOL/COMMENT
DATA ERROR
Editing the symbol and comment was interrupted by the power off or by the switch to the
CNC screen by the function key etc.
(solution) Please edit symbol and comment once on PMC.
Or, please input symbol and comment again.
B.2
LIST OF ALARMS
(PMC)