B–62073E–1/04 2. INTERFACE BETWEEN CNC AND PMC–NA OR NB
– 297 –
2.3.70 Simple synchronization control
Positional deviation check function
During simple synchronization, an OT alarm is issued when the difference between the positional deviations
for the synchronized axes (error counter value) is greater than the value set in a parameter. If this occurs in auto
matic operation, the movement is decelerated and stopped along all the axes. If this occurs in manual opera-
tion, the movement is decelerated and stopped only along the axes subject to simple synchronization. A signal
is al so issued in this case.
(1) During simple synchronization, alarm OT 513 is issued and output signal SYNER goes high when the dif-
ference between the positional deviations for synchronized axes (error counter value) is greater than the
value set in parameter No. 7799. If this occurs in automatic operation, the movement is decelerated and
stopped along all the axes. If this occurs in manual operation, the movement is decelerated and stopped
only along the axes subject to simple synchronization.
(2) Resetting the system under either of the following conditions cancels the alarm and sets output signal
SYNER to low:
1 When the axes are not synchronized
2 When the axes are synchronized and the difference between the positional deviations for synchro-
nized axes (error counter value) is less than the value set in parameter No. 7799.
– Excessive error alarm signal for simple synchronization: SYNER
[Classification]
Output signal
[Function] This signal goes high when the difference between the positional deviations for synchronized
axes (error counter value) is greater than the limit set in parameter No. 7799.
Resetting the system under either of the following conditions sets this signal to low:
1 When the axes are not synchronized
2 When the axes are synchronized and the difference between the positional deviations
for synchronized axes (error counter value) is less than the value set in parameter No.
7799