B–62073E–1/04 2. INTERFACE BETWEEN CNC AND PMC–NA OR NB
– 333 –
2.3.83 Ignore disconnect detector alarm in continuous velocity command of axis control by
PMC
When a servo motor is being controlled using a speed command, if the motor speed is too high, it becomes
impossible to receive position feedback pulses by hardware, and an alarm may be raised falsely to indicate
that a separate detector has been disconnected.
This function is used to ignore a signal indicating that a separate detector has been disconnected during the
speed command mode, thereby suppressing an alarm.
a) Hardware disconnection alarm clear signal NDCAL1, NDCAL2, NDCAL3, NDCAL4
[Classification]
Input signal
[Operation] When a signal changes from ”1” to ”0”, an internally detected hardware disconnection alarm
condition is cleared (not output to the outside).
NOTE These signals must be changed from ”1” to ”0” before the servo control mode is switched from
speed command to position command.
Signal NDCALx 1
0
PRM No.1954#7 1
0
Servo
mode
Speed command
Position command
During this period, the servo
control software ignores a
hardware disconnected condition.
Motor speed command0
CAUTION Once the servo control mode is switched from speed command to position command, a
manual return to the reference position must be made before the axis is driven.
NOTE This function cannot be used for a servo motor with an absolute–position detector.
2.3.84 Virtual axis control signal
(1) Signal for selecting the virtual axis control mode: IMGY
[Classification]
Input signal
[Function] Selects the virtual axis control mode.
[Operation] When the signal is set high, the system enters the virtual axis control mode.