B-64004EN/02 1.OVERVIEW
- 9 -
e) The simultaneous failure of two power transistors in the inverter
may cause the axis to briefly (motion depend on number of pole
pairs of motor)
Example:
An 8-pole synchronous motor can cause the axis to move by
a maximum of 45 degrees. With a lead-screw that is directly
driven by, e.g.16mm per revolution, this corresponds to a
maximum linear motion of approximately 2.0mm.
f) When a limit value is violated, the speed may exceed the set
value briefly or the axis/spindle overshoot the set point position
to a greater or lesser degree during the period between error
detection and system reaction depending on the dynamic
response of the drive and the parameter settings (see Section
Safety-Functions)
g) The category 0 stop function according to EN60204-1 (defined
as STOP A in Safety Integrated) means that the spindles/axes are
not braked to zero speed, but coast to a stop (this may take a very
long time depending on the level of kinetic energy involved).
This must be noted, for example, when the protective door
locking mechanism is opened.
h) Amplifiers (drive power modules) and motors must always be
replaced by the same equipment type or else the parameters will
no longer match the actual configuration and cause Dual check
Safety to respond incorrectly.
i) Dual check Safety is not capable of detecting errors in
parameterization and programming made by the machine tool
builder. The required level of safety can only be assured by
thorough and careful acceptance.
j) There is a parameter that MCC off test is not to be made in the
self test mode at power-on as in the case of machine adjustment.
This parameter is protected, only changed by authorized person.
IF MCC off test is not conducted, MCC may not be off at stop
response is measured.
k) Safety machine position monitoring function does not apply to
the spindle axis.
l) During machine adjustment, an exact motion may be executed
incorrectly until the safety functions setup correctly and confirm
test is completely.
m) Before the reference point return is performed and the MCC off
test is performed, it may be dangerous because the correct
operation does not be guaranteed. So, the careful operations are
required when the machine is operated in the status that the
protection door opens.
n) The delay timer is prepared for the cross-checking of the safety
related input/output signals. When the inconsistency exists
between the signal from the 2 paths, system will recognize this
failure, after this time is passed. The system will start the
sequence of MCC shut-off, when this time is passed after the
inconsistency is detected.