6.PARAMETERS B-64004EN/02
- 86 -
parameter, alarm PW0010, PW0011, PW0012 or PW0013 is
generated.
If a value of less than 16 is specified, it is assumed that 16 ms is
specified.
If a value of more than 1000 is specified, it is assumed that 1000 ms is
specified.
NOTE
The same value is applied to each path that
belongs to a machine group.
1946 MCC off Test timer
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Word machine group
[Unit of data] msec
[Valid data range] 0 to 32767
When MCC off Test mode is selected with Dual Check Safety
function, CNC CPU carries out MCC off Test by the safety output
signal (*MCF). If MCC off Test is not completed within the time set
in this parameter, a servo alarm SV0488 is generated.
If a value of less than 0 is specified, it is assumed that 10000 ms is
specified.
NOTE
The same value is applied to each path that
belongs to a machine group.
1948 MCC off timer 2
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Word machine group
[Unit of data] msec
[Valid data range] 0 to 32767
CNC CPU and PMC CPU set MCC Off signal (*MCFVx) to 0, when
an axis is not stopped within the time set by this parameter after Safe
Speed Monitoring or Safe Machine Position Monitoring function of
Dual Check Safety function detects abnormal condition.