3. INSTALLATION
B–63323EN/03
10
When a cabinet is designed, it must satisfy the environmental conditions
described in Section 3.1. In addition, the magnetic interference on the
screen, noise resistance, and maintenance requirements must be
considered. The cabinet design must meet the following conditions :
D The cabinet must be fully closed.
The cabinet must be designed to prevent the entry of airborne
dust,coolant,and organic solvent.
D The cabinet to hold the control unit must be designed to maintain a
difference in temperature of up to 10°C between the air in the cabinet
and the outside air when the temperature in the cabinet rises.
For details of the thermal design, see 3.4.
D A closed cabinet must be equipped with a fan to circulate the air
within. (This is not necessary for a unit with fan.)
The fan must be adjusted so that the air moves at 0.5 m/sec along the
surface of each installed unit.
CAUTION : If the air blows directly from the fan to the unit, dust
easily adheres to the unit. This may cause the unit to fail.
D For the air to move easily, a clearance of 100 mm is required between
each unit and the wall of the cabinet. (This is not necessary for a unit
with fan.)
D Packing materials must be used for the cable port and the door in order
to seal the cabinet.
D The LCD unit and MDI unit must not be installed in such a place that
coolant would directly fall onto the unit.
The front panels of the LCD unit and the MDI unit are dustproof.
However, avoid installing the units in locations where their front
panels directly receive coolant. For an explanation of the dust
protection measures for the power magnetics cabinets and pendant
boxes of machine tools, see Section 3.4.
D Noise must be minimized.
As the machine and the CNC unit are reduced in size, the parts that
generate noise may be placed near noise–sensitive parts in the
magnetics cabinet.
The CNC unit is built to protect it from external noise. Cabinet design
to minimize noise generation and to prevent it from being transmitted
to the CNC unit is necessary. See section 3.6 for details of noise
elimination/management.
D When determining the layout of units in the cabinet, consider
maintainability; arrange the units in such a way that they can be easily
replaced during maintenance and inspection.
D The hard disk drive and floppy disk drive must not be installed near
the source of a strong magnetic field.
D The installation conditions of the I/O unit and connector panel I/O
module must be satisfied.
To obtain good ventilation in the module, the I/O unit and connector
panel I/O module must be installed in the direction shown in the
following figure. Clearances of 100 mm or more both above and
below the I/O unit are required for wiring and ventilation.
Equipment radiating too much heat must not be put below the I/O unit
and connector panel I/O module.
3.3
DESIGN AND
INSTALLATION
CONDITIONS OF THE
MACHINE TOOL
MAGNETIC CABINET