11.TROUBLESHOOTING
737
Control unit
I/O module for connec-
tor panel
Allocated to
use a manual
pulse generator
Allocated to
use a manual
pulse generator
Group 0
Group 1
This manual pulse
generator I/F is
effective.
This manual pulse
generator I/F is not
effective.
Operator’s panel I/O
module
In this example, the manual pulse generator connected to the I/O module
for a connector panel in group 0 is effective.
Control unit
I/O module for connec-
tor panel
Allocated so as not
to use a manual
pulse generator
Allocated to
use a manual
pulse generator
Group 0
Group 1
This manual pulse
generator I/F is
effective.
This manual pulse
generator I/F is not
effective.
Operator’s panel I/O
module
If the I/O module for a connector panel in group 0 is allocated so as not
to use a manual pulse generator, as in this example, the manual pulse
generator interface of the operator’s panel I/O module in group 1 is
effective.
The allocation can be confirmed on the allocation edit screen. Selecting
[EDIT] and then [MODULE] from the PMC screen causes the allocation
edit screen to be displayed.
After editing allocation, write the changes to the FROM on the [I/O]
screen. Otherwise, the changes will be lost when the power is turned off.
If allocation is performed properly, when a manual pulse generator is
rotated, the bits count up/down in the area of the corresponding input
signal (X). Select [PMCDGN] and then [STATUS] from the PMC screen
to display the corresponding address, and rotate the manual pulse
generator to check that the bits count up/down.