(8) Analog output value is transferred to the specified AS-i slave
address bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
Y+17 2AH
Y+18
Slave address(01H~1FH) Note2) Refer as follows
Y+19 26 Ch1output value (High byte)
Y+20 27 Ch1 output value (Low byte)
Y+21 28 Ch2 output value (High byte)
Y+22 29 Ch2 output value (Low byte)
Y'+18 26 Ch3 output value (High byte)
Y'+19 27 Ch3 output value (Low byte)
Y'+20 28 Ch4 output value (High byte)
Set data
Y'+21 29
Ch4 output value (Low byte)
Response
data
X+25 Error code
Note) This command is only available in AS-i ver. 2.1.
Note1) How to input slave address
Kind of slave How to input slave address
A slave or standard slave Input address number (01~1FH) directly.
B slave Add 32(20hex) to address number, and input that
number.
example) In case of slave address is "10B".
10+32 --> 42 (2Ahex)
Input 42 (2Ahex) as address number.
Note2) In case of analog slave, input address number (01~1FH) directly. Because analog
slave is operated as standard slave without distinction of A/B slave.