4.PARAMETER SETTING START-UP B-65222EN/03
- 176 -
<7> Pressing the F1 key (to start measurement) at regular speed
displays the data shown below. (Check that the activating phase
angle-based sine waveform changes from negative to positive at
three points or more.)
CAUTION
Measurement direction varies with the setting of the
direction-of-movement parameter.
When the setting is 111: Measurement is
performed during forward movement.
When the setting is -111: Measurement is
performed during backward movement.
Measurement in the wrong direction hinders correct
calculation of the correction parameter.
TCMD
ctivating phase angle θ
<8> Pressing CTRL+L causes the correction parameter values to be
calculated as shown below. Enter the displayed parameter
values.
Usually, use the correction parameter values displayed on the top
row.
The parameter values displayed on the middle and bottom rows
are used for special parameter setting.
Middle row: To be used when either quadruple ripple correction
or quadruple TCMD output is selected.
Bottom row: To be used when both quadruple ripple correction
and quadruple TCMD output are selected.