5.TROUBLES AND CAUSES START-UP B-65222EN/03
- 180 -
5 TROUBLES AND CAUSES
The table below lists those troubles that often occur when a machine
with a linear motor mounted is started up, and their causes.
Trouble Possible cause
The coil slider is mounted upside down.
The linear motor does not
operate.
The power line is disconnected.
The power line connection is incorrect.
The signal line of the linear encoder is
disconnected.
Stop-time excessive error alarm
Loss of control
The AMR conversion coefficient is
incorrect.
Move-time excessive error
alarm
The power line connection is incorrect.
The power line connection is incorrect.
The coil slider is mounted upside down.
A very heavy load is imposed.
OVC (soft thermostat) alarm
The setting for cooling in the OVC
parameter is different.
The reference mark signal (reference
signal) output position is not within the
normal range.
Soft phase alarm
The reference mark signal includes noise.
The scale signal line is disconnected.
Disconnection alarm
The pole sensor signal line is disconnected.
The reference mark signal includes noise.
Count error alarm
The A/B phase signal includes noise.
α pulse coder soft
disconnection
(when an absolute
linear encoder is used)
Bit 7 of No. 1707 (FS15)/No. 2013 (FS16) is
set to 1.
NOTE
To protect against a malfunction and alarm arising
from noise, observe the following:
- Do not omit connector connections, but make
connector connections as specified (including
shielding).
- Do not relay an analog signal from the linear
encoder through a terminal block or the like.
- Make a ground connection securely between the
power distribution board (involving the NC and
amplifier) and the machine.
- Connect the shield of the feedback cable securely
to ground in the power distribution board.