3. TROUBLESHOOTING
B-65165E/02 TROUBLESHOOTING AND ACTION
- 119 -
3.1.1.7 Alarm code 07
(1) Meaning
In the main circuit, the DC voltage at the DC link is abnormally
high.
(2) Cause and troubleshooting
(a) Excessive regenerated power
Regeneration is impossible. The PSM does not have a
sufficient capacity.
→ Check the specification of the PSM.
(b) The output impedance of the AC power source is too high.
→ Check the power source output impedance.
(Normal if the voltage variation at maximum output time is
within 7%)
(c) Regeneration circuit failure
→ Replace the unit.
(d) The main circuit power supply may have been switched off
with an emergency stop state released.
→ Check the sequence.