M. PARAMETERS
B–66102E/10
APPENDIX
192
The compile parameters are initialized to the values set in the P–CODE
file at power–up. The parameters cannot be changed from MDI or others.
However, parameters 8547 and 8548, which are used for debugging, can
be set from MDI.
Bit No.
#7 #6 #5 #4 #3 #2 #1 #0Address
8500 LD6 R10 R05
R05
R10 Size of P–CODE file
R10 R05 Size of P–CODE file
0 0 256Kbyte
0 1 512Kbyte
1 0 1Mbyte
1 1 Not defined
LD6 = 1: This bit must always be set 1.
Bit No.
#7 #6 #5 #4 #3 #2 #1 #0Address
8502 NPE TMC EUI VAR DBG SBK DIR
DIR = 0 : The program list screen does not show P–CODE macro
program numbers.
= 1 : The program list screen shows P–CODE macro program
numbers.
NOTE
P–CODE macro program names cannot be displayed.
SBK = 0 : When the conversational macro or auxiliary macro is
executed with the debug function, continuous execution
is performed.
= 1 : When the conversational macro or auxiliary macro is
executed with the debug function, single–block
execution is performed.
DBG = 0 : The debug function is not used.
= 1 : The debug function is used.
VA R = 0 : The P–CODE macro variable screen cannot be displayed.
= 1 : The P–CODE macro variable screen can be displayed.
EUI = 0 : The P–CODE macro uses UI00 to UI15 and UO00 to
UO15 as UI/UO signals.
= 1 : The P–CODE macro uses EUI00 to EUI15 and EUO00
to EUO15 as UI/UO signals.
TMC = 0 : An execution macro call by a T code is a subprogram call
of O90000.
= 1 : An execution macro call by a T code is a macro call of
O90008.
NPE = 0 : Under RS–232–C control, % (EOF) is automatically
output.
= 1 : Under RS–232–C control, % (EOF) is not automatically
output.
M.1
SERIES 15i COMPILE
PARAMETERS