1.FACTOLINK FUNCTIONS FOR THE 16i/18i/21i III. SETTING B-63644EN/02
- 30 -
0813 Length of logging data
[Data type] Word
[Unit of data] Number of bytes
[Valid data range] 0 to 65535
Sets the length of the logging data.
0814 Logging trigger PMC address
[Data type] Word
[Valid data range] 0 to 65535
Sets the PMC address that constitutes the trigger for instructing the
transfer of logging data.
0815 Transmission interval of logging data
[Data type] Double-word
[Unit of data] Second
[Valid data range] 0 to 4294967295
Specifies the time interval at which logging data (fixed data only) is
sent. When "0" is specified, the logging data is sent only at connection.
0820 Name of machine to be reported to host (1st byte)
0821 Name of machine to be reported to host (2nd byte)
0822 Name of machine to be reported to host (3rd byte)
0823 Name of machine to be reported to host (4th byte)
0824 Name of machine to be reported to host (5th byte)
0825 Name of machine to be reported to host (6th byte)
0826 Name of machine to be reported to host (7th byte)
0827 Name of machine to be reported to host (8th byte)
0828 Name of machine to be reported to host (9th byte)
[Data type] Byte
[Valid data range] 32 to 126
Sets the machine name unique to each CNC that is needed so that the
host computer can identify each CNC. Set an alphanumeric and blank
ASCII code, in decimal.
#7 #6 #5 #4 #3 #2 #1 #0
3111 NPA
[Data type] Bit
NPA Performs the following if an alarm occurs while the FACTOLINK screen is
displayed.
1: Does not switch to the Alarm screen.
0: Switches to the Alarm screen.