# 4 ARL Tool life arrival notice signal TLCHB of tool life management is:
0: Output for each tool.
1: Output for the last tool of a group.
This parameter is valid only when bit 3 (GRP) of parameter No. 6802 is set to 1.
# 5 TGN In the tool life management function, the optional group number
function is:
0: Not used.
1: Used.
NOTE
When the optional group number function is used, bit 4 (LFB) of
parameter No. 6805 must be set to 1 to enable the tool life
management B function.
In lathe systems, the optional group number function can be
used if the tool change type is the ATC type (bit 3 (TCT) of
parameter No. 5040 = 1).
# 6 TSK If the count type in tool life management is the duration type, then
when the last tool of a group is skipped by a signal:
0: The count value for the last tool equals the life value.
1: The count value for the last tool remains unchanged.
# 7 RMT Tool life arrival notice signal TLCHB is turned on and off as follows:
0:
The signal is turned on if the remaining life value (the life value minus the life
counter value) is smaller than or equal to the remaining life setting. The
signal is turned off if the remaining life value (the life value minus the life
counter value) is greater than the remaining life setting.
1:
The signal is turned on if the remaining life value (the life value minus the life
counter value) is equal to the remaining life setting. The signal is turned off
if the remaining life value (the life value minus the life counter value) is not
equal to the remaining life setting.
NOTE
When using the life count override feature, set bit 7 (RMT) of
parameter No. 6802 to 0. When the life count is specified by
duration, the unit used for determining the result of comparison
between the remaining life and the remaining life setting varies
depending on the life count interval (bit 0 (FCO) of parameter
No. 6805). If the life is counted every second, the comparison
is made in units of 1 minute; if the life is counted every 0.1
second, the comparison is made in units of 0.1 minute.
#7 #6 #5 #4 #3 #2 #1 #0
6804
TCI
[Input type] Parameter input
[Data type] Bit path