If manual handle operation cannot be performed, the probable causes
include the following:
D The servo is not activated.
D Manual pulse generators are not connected properly to the built–in I/O
port or I/O module.
D The I/O link of the built–in I/O port or I/O module is not allocated, or
is not allocated properly.
D A related input signal is not input due to a parameter setting error.
Check that the LED on the servo amplifier indicates “0”. If a number
other than “0” is indicated, the servo is not activated. In this state, even
JOG operation and automatic operation cannot be operated.
Check the servo–related parameters and the wiring.
(1)Cable failures (such as breaks)
Examine the cables for faults such as breaks and short–circuits,
referring to the figure below.
For Series 0i–B
#1
#2
#3
MPG
(JA3)
CNC
Built–in I/O board
First manual
pulse generator
Second manual
pulse generator
Third manual
pulse generator
For Series 0i Mate–B
#1
#2
#3
JA3
IOLINK
JD1B
(JD1A)
CNC Operator’s panel I/O module
First manual
pulse generator
Second manual
pulse generator
Third manual
pulse generator
8.4
HANDLE OPERATION
CANNOT BE DONE
Causes and actions
1 The servo is not
activated
2 Checking the manual
pulse generators