B–63523EN/03
7. SERVO INTERFACE
163
1) Notes on installation
(1)Use an interface unit in a completely enclosed cabinet.
(2)Install an interface unit on a vertical surface, and provide a space
of 100 mm above and below the unit. Below an interface unit, do
not place equipment that generates a large amount of heat.
(3)When using a basic unit and expansion unit, place the units as
shown below so that the flat cable connecting the units does not
block the vent holes. A flat cable not longer than 100 mm must be
used.
Vent holes
Flat cable
Basic unit Expansion unit
2) Installation using screws
Basic unit Expansion unit
When using both a basic unit and expansion unit, install the units as
shown above, with the mounting holes horizontally separated by 70
to 80 mm.
7.1.12
Installation