B--63003EN--1/02
1. AXIS CONTROL
163
1.Synchronous, composite, or superimposed control cannot be started,
but no alarm is issued.
(1)The synchronous or composite control option has not been
specified.
The synchronous and composite control must be specified.
(2)The G0128, G0138, G0190, G1128, G1138, or G1190 signal has
not risen.
Synchronous, composite, or superimposed control begins on
the positive--going edge of the G0128, G0138, G0190, G1128,
G1138, or G1190 signal. If synchronous, composite, or
superimposed control ends because of a reset or alarm, merely
releasing the reset or alarm cannot restart synchronous,
composite, or superimposed control. It is also necessary to raise
the signal.
(3)The axis number of an axis to be subjected to synchronous,
composite, or superimposed control has not been specified in a
parameter.
To use synchronous control, specify the axis number of the
target master axis in parameter No. 8180. To use composite
control, specify the axis number of the target axis in parameter
No. 8183 of path 2. To use superimposed control, specify the
axis number of the target master axis in parameter No. 8186.
(4)Synchronous, composite, or superimposed control cannot be
started when the NC unit is under one of the following conditions.
S Emergency stop
S Reset
S Servo alarm
S P/S000 alarm
S Alarm related to synchronous, composite, or superimposed
control
In addition, synchronous, composite, or superimposed control
cannot be started when the NC unit is under one of the following
conditions.
S Servo--off
S Overtravel
1.9.10
Troubleshooting