B--63003EN--1/02
4. REFERENCE POSITION ESTABLISHMENT
369
1850 Grid shift for each axis
[Data type] Two--word axis
[Unitofdata] Detection unit
[Valid data range] --99999999 to 99999999
A grid shift is set for each axis.
To shift the reference position, the grid can be shifted by the amount set in
this parameter. Up to the maximum value counted by the reference
counter can be specified as the grid shift.
NOTE
When this parameter has been set, the power must be
turned off before operation is continued.
#7
3003
#6 #5
DEC
#4 #3 #2 #1 #0
[Data type] Bit
DEC Deceleration signal (*DEC1 to *DEC8) for manual reference position
return
0 : Deceleration is applied when the signal is 0.
1 : Deceleration is applied when the signal is 1.
Number Message Description
090 REFERENCE RETURN
INCOMPLETE
The reference position return cannot
be performed normally because the ref-
erence position return start point is too
close to the reference position or the
speed is too slow. Separate the start
point far enough from the reference
position, or specify a sufficiently fast
speed for reference position return.
Check the program contents.
091 REFERENCE RETURN
INCOMPLETE
Manual reference position return can-
not be performed in the feed hold state.
Perform a manual reference position
return in the automatic operation stop
state or reset state.
224 RETURN TO
REFERENCE POINT
Not returned to reference point before
cycle start. (Only when parameter
ZRNx (No. 1005#0).
Do reference position return.
Alarm and message